Connectors Technical Information

Modified on Tue, 9 Mar, 2021 at 12:21 PM

Connectors Technical Information


Summary: The Connectors plugin handles hangers for wood member connections to other wood members, concrete/masonry walls, steel beams, and wood nailers.

The Connectors plugin uses Simpson Strong-Tie’s connector capacity information from their “Wood Construction Connectors” catalog (2019-2020).

Connectors plugin Walk-through and usage guide

Connector Demand (Loads)

  • ASD Load Combinations

    • The Connectors plugin uses Allowable Stress Design (ASD) load combinations, even if Load and Resistance Factor Design (LRFD) is chosen for the member. 

    • This is because Simpson Strong-Tie’s catalog values use ASD. 

    • You can still design the member using LRFD, and the plugin will use the unfactored support reactions to create the ASD factored loads for connectors. 

  • Duration Factor Load Groups

    • The loads are run through every ASD load combination, and the resulting factored ASD loads are sorted into 10 duration factor groups (5 for positive/downward and 5 for negative/uplift conditions) based on the highest duration factor needed for that combination. 

    • The duration factor groups that the load combinations are grouped into are:

      • CD = 0.9 for dead load

      • CD = 1.0 for live load

      • CD = 1.15 for snow, rain and ice loads

      • CD = 1.25 for roof live loads

      • CD = 1.60 for wind and seismic loads

    • The resulting loads from the ASD combinations are sorted based on the highest duration factor required in a given combination.  For example:

      • D+L would be part of the CD = 1.0 group for live loads

      • D+0.75L+0.75Lr would be part of the CD = 1.25 group for roof loads

      • D+0.75L+0.75S would be part of the CD = 1.15 group for roof loads

    • The largest load for each of the 10 duration factor groups is saved for comparison with the corresponding 10 capacities, derived from the catalog tables (see below).

Connector Capacity

  • Catalog Duration Factor Capacity Groups

    • Typically the Simpson catalog values include cases for Uplift (CD = 1.6), Floor (CD = 1.0), Snow (CD = 1.15) and Roof (CD = 1.25). 

    • The Connectors plugin takes these catalog capacity values and extrapolates them into the additional groups as appropriate.

      • For example, typically the uplift case given is for a duration factor of 1.6, which assumes the uplift is from wind/seismic loading.  These values are then reduced by the appropriate duration factors to come up with the capacity for other load cases.  So for uplift that is from dead load only, the capacity for that case would be multiplied by a factor of 0.9/1.6 = 0.5625.

    • Capacity reductions such as these are always applied, but capacity increases are only applied if the catalog indicates that this is appropriate. 

      • For example, if a downward Roof (CD = 1.25) capacity is given, but not a capacity for downward Wind (CD = 1.6), then the Roof capacity is conservatively used for the Wind cases as well, without an increase. But where the catalog indicates that increases are allowed, they are applied.


  • Catalog Capacity Adjustment Factors (Slope, Skew, Top Flange Conditions)

    • Connector capacities are automatically adjusted by the factors given in Simpson Strong-Tie’s catalog, such as for sloped and skewed seats and various top flange conditions. 

    • These factors are typically given in notes, footnotes, or tables for each hanger type in the catalog. 

    • In some cases, where the catalog includes options that aren’t covered in the program (such as square cut vs bevel cut members), the most conservative appropriate factor is applied. 

    • In other cases where actual maximum load values are given instead of adjustment factors, the adjustment factors are back-calculated based on the values given.

Additional Capacity Adjustments and Limitations

  • Species Adjustment Factor

    • Where a different species of wood than those indicated in the catalog is used for either the supporting or the hanging member, the connector capacities are adjusted based on the specific gravity of the members (per note ‘f’ on page 17 of the catalog).

  • Hanger Width Limitations

    • The list of passing connectors is limited to hangers that are no more than 1” wider than the member (or ⅛” wider for I-joists). The designer should review the conditions for each beam, and provide shims where appropriate.

  • Hanger Height Limitations

    • The height (depth) of the supporting member must be at least as big as the height of the hanger for Face-Mount and Concealed hangers, and for Top-Flange hangers that have a specific minimum height requirement.

  • Web Stiffeners

    • Most I-joist hangers require web stiffeners, and the name of the hanger will reflect “WSR” (web stiffeners required). 

    • Those that do not require web stiffeners typically require that the top flange be braced by the hanger.  

    • If a hanger does not require web stiffeners, it is only included in the list if it is within 1” above or below the I-joist depth to ensure that the joist is able to be braced by the connector.  The designer should review these connectors to ensure that the I-joist is appropriately braced by the hanger in these situations, or provide web stiffeners where needed.

  • Fastener Length

    • Where the supporting member width is too narrow for the required fastener length (based on the fasteners specified in the catalog), the appropriate reduction factor is applied for shorter fasteners to be used where indicated in the catalog.

    • If no adjustment factor is given, the connector is removed from the list of allowable connectors if the supporting member is too narrow for the fasteners.

  • Top Flange Width

    • The supporting member must be wide enough to support the full top flange width for a top-flange hanger to be included in the list.

Analyzing Results/Outputs

Results Screen

  • Demand (Loads)

    • The results screen displays the loads for the 5 most common duration factor groups at the top.

    • The other duration factor groups are used in the calculations but not displayed.

  • Capacity (Passing Connectors)

    • The results screen also displays the capacity of passing hangers for the 5 most common duration factor groups.

    • The other duration factor groups (including back-calculated groups mentioned above) are used in the calculations, but not displayed.

  • Adequacy

    • The adequacy percentage is listed for each passing connector, and is calculated using the 10 duration factor demands with their corresponding 10 duration factor capacities.

Print Preview

  • Custom Conditions

    • The Print Preview includes a Connectors table with the name of the hanger and the alternates, as well as the other custom conditions set by the user (skew, slope, top flange conditions, etc). 

  • Specifications Information

    • Where custom conditions are used, an additional line at the bottom will include the required additions to the hanger specification.

      • These will say things like “X SKL20” where the “X” indicates special conditions, and the “SKL20” indicates the hanger is skewed left 20 degrees. See page 97 of the Simpson catalog. 

      • Note that if a hanger comes with a standard skew built in, the skew need not be added to the hanger spec (for example, the SUR/L and HSUR/L hangers come with a 45 degree skew standard).

      • For some hangers the height is also required, and the designer will need to add the height to the specification using the format “H=___”.

    • Where a connector name includes “R/L” for right/left skews, only the direction of the skew needed for that hanger needs to be included in the spec.  

      • For example, an HSUR/L that has skew to the left would be specified “HSUL”.

Other Information

  • Hangers to Concrete/Masonry Walls
    • The HU/HUC/HSUR/L hangers do not allow slope or skew options at concrete/masonry walls because Simpson's Catalog does not list adjustment factors for these options in the concrete/masonry section.
    • Edge and end distances for concrete/masonry hangers are not checked by the program, and still need to be checked by the designer based on the limitations in the Simpson Catalog.
  • Hangers to Steel Beams
    • Uplift capacities for hangers to steel beams come from Simpson's T-C-WELDUPLFT document, and require the minimum welded connections per this document.
    • The capacities listed in the above-referenced document are not species specific, and are therefore used for both DF and SPF capacities.
  • Hangers to Wood Nailers
    • Capacities for hangers to wood nailers come from Simpson's T-C-NAILUPLFT document and are based on the nailer sizes shown in the table. Any other nailer size will result in a capacity of 0.


If you have any questions or suggestions, please don't hesitate to reach out to our customer service at support@thevitruviusproject.com. Thanks for reading!


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article